Mobile ESS - Power Hub Model
• Battery System - Cabinet (420kWh) / standard 20ft HQ (1000kWh or 2000kWh) / Customization, customised compact Cabinet mounted on double/single-axle compact trailer, towed by light Vehicle, complying with local traffic regulations
• Power Hub System - Cabinet 250kW / 500kW / 1000kW / 1500kW / Customization
• All Terrains - Road vibration protection , damping mat, EV level battery & pack. Safe to transport, under full charge condition, at any road condition
• Fast Deployment – compact, easy to set up, no need to disconnect power in transportation. After arriving on site system, system can be running within few minutes, reducing on site activities and high reliability
• Mature thermal solution with liquid cooling and precision air conditioner for extremely cold/hot environment -35℃ ~ +60℃
• Outside maintenance, no space limitation for maintenance & installation comparing with inside maintenance design
• Simplified control panel design, to operate the system outside and avoid electric shock hazard
• High quality components (ABB/Schneider/etc.) to support high power/current
• Scalable design to supports up to 4 parallel modulars, easy system expansion
• Auxiliary power supply for system shut down
• Off-grid, Micro-grid, On-grid - Easy for positioning and wiring, plug and play,
• FFS: FM-200 (Novec 1230 Optional)
• IP55, C5 or C3
• Design to UL, CE, IEC
250kW Power Hub + 420kWh Trailer | 500kW Power Hub+1000kWh Container | 1000kW Power Hub+2000kWh Container | |
System Parameters |
|||
View |
|||
Application |
Off-grid /On-grid / Micro-grid |
||
Rated Power/Energy |
250kVA AC Output + 420kWh ESS |
500kVA AC Output + 1000kWh ESS | 1000kVA AC Output + 2000kWh ESS |
Dimension (L*W*H) |
4000x 1500 x 1300mm |
10ft DG |
20ft HQ |
Weight |
5Tons |
12Tons | 23Tons |
Output Isolation |
Isolation Transformer |
Isolation Transformer | Isolation Transformer |
Noise |
<75dB |
||
Operating Temperature |
-20℃ ~ +60℃ (50-60℃ with derating) |
||
Humidity |
≤95%, no condensing |
||
Cooling/Heating |
System level: Outdoor Air conditioner Battery system: Liquid cooling and PTC heating Electronic cabinet: Air conditioner |
||
Ingress protection |
Power Hub IP54 / Battery IP65 |
||
Expected lifetime |
10+ years |
||
Warranty |
System 2years, Battery 5years, Electronic parts 2 years |
||
Designed to |
UL, UN38.3, CE, IEC |
||
AC Parameters | |||
Rated AC Power |
250kVA |
500kVA |
1000kVA |
Rated AC Output Voltage |
480V (U/V/W/PE)-NA, 400V (U/V/W/N/PE)-EU | 480V (U/V/W/PE)-NA, 400V (U/V/W/N/PE)-EU | 690(3W+PE) |
Frequency |
50/60 (-2.5~2.5) Hz |
50/60 Hz ± 2.5Hz |
50/60 Hz ± 2.5Hz |
THDi |
≤3% |
≤1.5% | |
Power Factors |
0.99 leading ... 0.99 lagging |
||
Battery Parameters | |||
Battery Capacity |
420kWh | 1000kWh | 2064kWh |
Battery Type |
LFP 280Ah |
||
Operating DC Voltage |
672V – 876V |
600-900V |
600-900V |
Maximum Charge/Discharge Capacity |
0.5C/ 0.5C |